Details and Size
Specification | Housing Material | ASTM A183 | |
---|---|---|---|
Product Name | Seismic Isolation Joints | Gasket Material | EPDM |
Product No. | HP-FC01 | Size | 40A~200A |
Applications | Flexible (Seismic) | ||
Stationary (General piping) |
Seismic Isolation Joints Installation Example 1
Seismic Isolation Joints Installation Example 2
Seismic Isolation Joints Installation Example 3
Seismic Isolation Joints Installation Guidelines
-
diameter Sleeve Standard 50A 80mm 65A 100mm 80A 125mm 100A 150mm 125A 200mm 150A 250mm 200A 300mm
- Install within 0.6m from the ceiling, 0.3m from the floor for larger than two-story building
- Install top/ bottom of alarm valve, preaction valve
- Install on T section that goes from standing line to secondary side of alarm valve
- Install on the line that goes from standing line to horizontal line.
- Install one seismic isolation joints for standing line of 0.9 to 2.1m (two joints for longer than 2.1m, unnecessary for less than 0.9m)
- Apply seismic isolation joint for lines than penetrate walls (within 30m from each dimension) or secure separation distance
- Apply seismic isolation joint within 0.6m from the end of reclamation.