Details and Size

Specification Housing Material ASTM A183
Product Name Seismic Isolation Joints Gasket Material EPDM
Product No. HP-FC01 Size 40A~200A
Applications Flexible (Seismic)
Stationary (General piping)
  • Seismic Isolation Joints Installation Example 1

  • Seismic Isolation Joints Installation Example 2

  • Seismic Isolation Joints Installation Example 3

Seismic Isolation Joints Installation Guidelines

  • diameter Sleeve Standard
    50A 80mm
    65A 100mm
    80A 125mm
    100A 150mm
    125A 200mm
    150A 250mm
    200A 300mm
  1. Install within 0.6m from the ceiling, 0.3m from the floor for larger than two-story building
  2. Install top/ bottom of alarm valve, preaction valve
  3. Install on T section that goes from standing line to secondary side of alarm valve
  4. Install on the line that goes from standing line to horizontal line.
  5. Install one seismic isolation joints for standing line of 0.9 to 2.1m (two joints for longer than 2.1m, unnecessary for less than 0.9m)
  6. Apply seismic isolation joint for lines than penetrate walls (within 30m from each dimension) or secure separation distance
  7. Apply seismic isolation joint within 0.6m from the end of reclamation.