Details and Size

Specifications Material STEEL(Carbon Steel)
Product Name Lateral/Longitudinal Bracing Size 40A~200A
Product No. HP-A01 Installation Angle 30˚~ 90˚
KFI Certification No. Bracing 19-36
  • Longitudinal Bracing Construction Example 1

  • Longitudinal Bracing Construction Example 2

  • Longitudinal Bracing Construction Example 3

  • Longitudinal Bracing Construction Example 4

Longitudinal Bracing Installation Guidelines

  1. Install within 12m from the end of the main line (water hammer arrestor).
  2. Maximum interval between bracings is 24m.
  3. Possible to exclude when length from the top of the main run to the fixed part (slab, ceiling) is less than 150mm
Rated Load Installation Angle Allowable Load by Angle Applicable Horizontal Force
7,117N 30˚~44˚ 363.11kg ~ 504.44kg Below 363kg
45˚~59˚ 513.51kg ~ 622.52kg Below 513kg
60˚~89˚ 628.91kg ~ 726.15kg Below 628kg
90˚ 726.22g Below 726kg