Details and Size
Specifications | Material | STEEL(Carbon Steel) | ||
---|---|---|---|---|
Product Name | Lateral/Longitudinal Bracing | Size | 40A~200A | |
Product No. | HP-A01 | Installation Angle | 30˚~ 90˚ | |
KFI Certification No. | Bracing 19-36 |
Longitudinal Bracing Construction Example 1
Longitudinal Bracing Construction Example 2
Longitudinal Bracing Construction Example 3
Longitudinal Bracing Construction Example 4
Longitudinal Bracing Installation Guidelines
- Install within 12m from the end of the main line (water hammer arrestor).
- Maximum interval between bracings is 24m.
- Possible to exclude when length from the top of the main run to the fixed part (slab, ceiling) is less than 150mm
Rated Load | Installation Angle | Allowable Load by Angle | Applicable Horizontal Force |
---|---|---|---|
7,117N | 30˚~44˚ | 363.11kg ~ 504.44kg | Below 363kg |
45˚~59˚ | 513.51kg ~ 622.52kg | Below 513kg | |
60˚~89˚ | 628.91kg ~ 726.15kg | Below 628kg | |
90˚ | 726.22g | Below 726kg |