상단메뉴 바로가기 본문 바로가기 본문 하위메뉴 바로가기 하단 바로가기

Details and Size

Specifications Material STEEL(Carbon Steel)
Product Name Lateral/Longitudinal Bracing Size 40A~200A
Product No. HP-A01 Installation Angle 30˚~ 90˚
KFI Certification No. Bracing 19-36
  • Lateral Bracing + Lateral Bracing Construction Example 1

  • Lateral Bracing + Lateral Bracing Construction Example 2

  • Lateral Bracing + Lateral Bracing Construction Example 3

  • Lateral Bracing + Lateral Bracing Construction Example 4

4-Way Bracing Installation Guidelines

  1. Interval between bracings should within 8m
  2. Install 4-way bracing for standpipe exceeding 1m
  3. Install within 0.6m of the highest top of standpipe that exceeds 1m
  4. In the case of having difficulty installing on vertical piping, install on horizontal piping within 0.6m of vertical piping criteria. (install one lateral, longitudinal each)
  5. In the case of having difficulty installing on pump discharge part of vertical piping, install referring to the guideline 4.